
20
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x: ( 514) 321-4150
028-0427-01 www.viconics.com | sales@viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
VT8300 Series
User Interface Guide
CONFIGURATION PARAMETERS SCREEN 3/7
These parameters are only displayed on
models with built in humidity
sensor
PARAMETER DETAILS SCREEN 3/7
Configuration Parameters Default Value Significance and Adjustments
Standby time
Default value: 0.5 hours
Standby Time
Time delay between the moment where the PIR cover detects
last movement in the area, and the time which the Terminal Equipment
Controller stand-by setpoints become active.
Range: 0.5 to 24.0 hours in 0.5 hours increments.
Unocc. time
Default value: 0.0 hours
Unoccupied Time
Time delay between the moment where the Terminal Equipment
Controller toggles to stand-by mode, and the time which the Terminal
Equipment Controller unoccupied mode and setpoints become active.
Factory value 0.0 hours: Setting this parameter to its default value of
0.0 hours disables the unoccupied timer. This prevents the Terminal
Equipment Controller to drift from stand-by mode to unoccupied mode
when PIR functions are used.
Range: 0.0 to 24.0 hours in 0.5 hours increments.
Komentarze do niniejszej Instrukcji