Viconics VT8300 Low Voltage User Interface Guide Instrukcja Użytkownika Strona 16

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 45
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 15
16
Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fa x: ( 514) 321-4150
028-0427-01 www.viconics.com | sales@viconics.com November 2014
© 2014 Viconics Technologies Inc. All rights reserved.
VT8300 Series
User Interface Guide
PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
UI 16
Universal input no.1 configuration
Default value = None
Universal Input No. 1
None: no function associated with input
Rem NSB: remote NSB timer clock input. The scheduling gets set as
per the binary input and provides low cost setback operation via a dry
contact.
Motion No and Motion NC: advanced PIR occupancy functions using
a Normally Open (NO) or Normally Closed (NC) remote PIR motion
sensor.
Window EMS: forces system to disable any current heating or
cooling action by Terminal Equipment Controller.
UI 17
Universal input no.2 configuration
Default value = None
Universal Input No. 2
None: no function associated with input.
Door Dry: door contact and motion detector.
Override: temporary occupancy remote override contact.
Filter: backlit flashing filter alarm shows on the Terminal Equipment
Controller LCD screen when the input is energized.
Service: backlit flashing Service alarm shows on Terminal Equipment
Controller LCD screen when input is energized.
1/7 Configuration
UI 19
UI 17
UI 16
None
None
None
Occupancy src
Motion
Smart recovery
Off
Setpoint func.
Attach Stp
CONFIGURATION PARAMETERS SCREEN 1//7
Przeglądanie stron 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 44 45

Komentarze do niniejszej Instrukcji

Brak uwag