Parameter Variable Name Function
Name Valid Range Default value
di1 config 0 = None
1 = RemNSB
2 = RemOVR
3 = Filter
4 = Service
0 = None
di2 config 0 = None
1 = RemNSB
2 = RemOVR
3 = Filter
4 = Service
0 = None
aux contact config 0 = NORMALLY_OPEN
1 = NORMALLY_CLOSE
0
number of events 2 or 4 2
progressive recovery 0 = Off
1 = Active
0 = Off
a.hp rev valve config 1 = Normally Heat
2 = Normally Cool
2
a.number of heating
stages
1 = 1 Stage
2 = 2 Stages
2
number of cool or hp
stages
1 = 1 Stage
2 = 2 Stages
2
econo min position 0 to 100% 0%
b.hp high balance
point
34 to 90°F (1 to 32°C) 90°F
b.econo changeover
setpoint
14 to 70°F (-10 to 21°C) 55°F
c.hp low balance
point
-40 to 30°F(-40 to –1°C) -12°F
c.econo mixed air
setpoint
50 to 90°F (10 to 32°C) 50°F
d.hp comfort or
economy mode
0 = Comfort
1 = Economy
0 = Comfort
d.econo mechanical
cool enable
0 = Off
1 = On
0 = Off
Thermostat’s
common
configuration
parameters
network input
config
UNVT_cfg
_
2_rtu_hp
nciCfg2RtuHpt
hp compressor
auxheat interlock
0 = Off
1 = On
0 = Off
This configuration property helps the user identify the type of equipment
being monitored.
Valid Range:
Value Identifier Name
HVAC Unit-
Type
Identifier
network input
config
SNVT_hvac_type
nciHvacType
0
1
2
3
4
5
6
7
8
9
HVT_GENERIC – Not Used
HVT_FAN_COIL
HVT_VAV –
Not Used
HVT_HEAT_PUMP
HVT_ROOFTOP
HVT_UNIT_VENT –
Not Used
HVT_CHIL_CEIL – Not Used
HVT_RADIATOR –
Not Used
HVT_AHU –
Not Used
HVT_SLF_CONT – Not Used
Generic
Fan Coil
Variable Air Volume Terminal
Heat Pump
Rooftop Unit
Unit Ventilator
Chilled Ceiling
Radiator
Air Handling Unit
Self-Contained Unit