Typical applications
Schematic Wiring Settings
2 pipe system cooling and/or heating: VT7300A5x00(x), VT7300C5x00(x) & VT7305C5x00(x) On / Off N.C. actuator
Mandatory
Pipe no = 2 pipes
CntrltTyp = On/Off
Fan Menu = 0 (L-M-H)
FL time = as per actuator
If cooling only set::
SeqOpera = 0 Cooling only
If heating only set::
SeqOpera = 1 Heating only
If heat / cool auto-changeover with
a local water temperature sensor set:
SeqOpera = 0 Cooling only
UI3 = COS
2 pipe system cooling and/or heating: VT7300C5x00(x) & VT7305C5x00(x) Floating actuator
Mandatory
Pipe no = 2 pipes
CntrltTyp = Floating
Fan Menu = 0 (L-M-H)
FL time = as per actuator
If cooling only set::
SeqOpera = 0 Cooling only
If heating only set::
SeqOpera = 1 Heating only
If heat / cool auto-changeover with
a local water temperature sensor set:
SeqOpera = 0 Cooling only
UI3 = COS
2 pipe system cooling and/or heating: VT7300F5x00(x) & VT7305F5x00(x) Analog actuator
Mandatory
Pipe no = 2 pipes
Fan Menu = 0 (L-M-H)
RA/DA = as per actuator
If cooling only set::
SeqOpera = 0 Cooling only
If heating only set::
SeqOpera = 1 Heating only
If heat / cool auto-changeover with
a local water temperature sensor set:
SeqOpera = 0 Cooling only
UI3 = COS
0 to 10
Vdc
UI3 COS
0 V~ Com
24 V~ Hot
AO1
Optional supply water
temperature sensor
Fan-L
Fan-M
Fan-H
High
Med
Low
24 Vac fan relays
Modulating Analog
Valve Cooling and/or Heating
Room Temperature
Control Thermostat
3 Speed fan
Modulating Floating
Valve Cooling and/or Heating
Room Temperature
Control Thermostat
3 Speed fan
Optional supply water
temperature sensor
UI3 COS
24 V~ Com
24 V~ Hot
BO1 Open
BO2 Close
Fan-L
Fan-M
Fan-H
High
Med
Low
24 Vac fan relays
Normally Closed On/Off
Valve Cooling and/or Heating
Room Temperature
Control Thermostat
3 Speed fan
Optional supply water
temperature sensor
UI3 COS
24 V~ Com
24 V~ Hot
BO2 N.C.
Fan-L
Fan-M
Fan-H
High
Med
Low
24 Vac fan relays