VT8600 SeriesUser Interface Guide
32
Viconics Technologies Inc. 9245 Langelier Blvd. Saint-Leonard, Quebec, Canada, H1P 3K9 I +1 514 321 5660
028-0441-00 www.viconics.com November 2014
© 2014 Viconics Technologies. All rights reserved.
SETPOINT SETTINGS 2/2
SETPOINT PARAMETER DETAILS
Configuration Parameters Default Value Significance and Adjustments
Default heat
Default value: 22.0 °C (73 °F)
Default Heat
Used for hospitality applications in stand-alone mode only. When
devices are in deep unoccupied mode, any movement detected by
PIR resets actual occupied set points to fresh room default setting.
Default setpoint is used to write to Heating setpoint when
thermostat goes to Unoccupied mode.
Cooling setpoint is set according to Min. deadband; 18.0 to 26.5
°C (65 to 80 °F).
Parameter is only used when Stand-by mode = Rel.
Min. deadband
Default value: 1.5 °C (3 °F)
Minimum Deadband
Minimum deadband value between heating and cooling setpoints
applied only when any setpoints are modified.
Range: 1.0 to 2.5 °C, 0.5 °C increments (2, 3, 4 or 5 °F, 1.0 °F
increments).
Max heating
Default value: 32 °C (90 °F)
Maximum Heating
Maximum occupied and unoccupied heating setpoint adjustment.
Range: 4.5 to 32.0 °C (40 to 90 °F).
Min. cooling
Default value: 12.0 °C (54 °F)
Minimum Cooling
Minimum occupied and unoccupied cooling setpoint adjustment.
Range: 12.0 to 37.5 °C (54 to 100 °F).
Supply air SP
Default value: 13.0 °C (55 °F)
Free cooling supply air setpoint when economizer mode is
enabled.
50 to 90 °F (10.0 to 32.0 °C)
Min. SH
Only valid if HT Type is set to Analog
Minimum supply heat temperature setpoint
Default value: 18.0 °C (64 °F)
Sets the minimum supply heat to be maintained by the
controller during occupied periods (Occupied or Temporary
Override).
From 50 °F up to 72 °F (10 °C up to 22 °C)
(increments: 0.5° or 5°)